北海JCZ1F

The company, with its strong technical force, complete equipment testing, mature production processes, rich technical experience, strict product quality assurance, sincere service attitude and after-sales service, provides users with excellent and distinctive products and services.

Product Description

Technical Parameters:

Name

JCZ1-

160/12

JCZ1-

250/12

JCZ1-

400/12

JCZ1-

630/12

Main Circuit Rated Voltage (KV)

Maincircult rated voltage(KV)

12

12

12

12

Main Circuit Rated Current (A)

Maincircultratedcurrent(A)

160

250

400

630

Main Circuit Making Capacity (A/100 times)

Maincircultmakingability(A/100ops.)

1600

2500

4000

4000

Main Circuit Breaking Capacity (A/100 times)

Maincircultbreak-makingability(A/100ops.)

1280

2000

3200

5000

Ultimate Breaking Capacity (A/3 times)

Maximumbreakability(A/3次)

3200

4000

4500

6000

Main Circuit Power Frequency Withstand Voltage (Open Circuit) 1min (KV)

PowerFrequencyVoltage-Withstand(KV)

42

42

42

42

Mechanical Life (times)

Mechanical life(ops.)

1000000

1000000

1000000

1000000

Electrical Life AC3 (times)

Electrical life AC3(ops.)

300000

300000

300000

300000

Electrical Life AC4 (times)

Electrical life AC4(ops.)

50000

50000

50000

50000

Rated Operating Frequency AC3 (times/h)

RatedoperatefrequencyAC3(ops./h)

300

300

300

300

Rated Operating Frequency AC4 (times/h)

RatedoperatefrequencyAC4(ops./h)

120

120

120

120

Terminal Pressure (N)

Terminal pressure(N)

>200

>200

>200

>200

Contact Gap (mm)

Clearancebetweenopencontacts(mm)

5±0.5

5±0.5

5±0.5

5±0.5

Overtravel (mm)

Overtravel(mm)

1.5±0.2

1.5±0.2

1.5±0.2

1.5±0.2

 

 

JCZ1F Permanent Magnet Series Single-Pole Outline Structure and Installation Dimensions