北海JCZ5-12D

The company, with its strong technical force, complete equipment testing, mature production processes, rich technical experience, strict product quality assurance, sincere service attitude and after-sales service, provides users with excellent and distinctive products and services.

Product Description

Technical Parameters:

Model

160A

250A

400A

630A

Technical Characteristics

Difference Name

Rated Operating Voltage (KV)

7.2/12

Rated Operating Current (A)

160

250

400

630

Rated Make Capacity (A/100 times)

1600

2500

4000

6300

Rated Breaking Capacity (A/25 times)

1280

2000

3200

5000

Ultimate Breaking Capacity (A/3 times)

4000

4000

5000

6300

Power Frequency Withstand Voltage of Breaking Point (KV)

32/42

Phase-to-Phase and Phase-to-Ground Power Frequency Withstand Voltage (KV)

32/42

Lightning Impulse Withstand Voltage (KV)

60/75

Main Circuit Contact Resistance (μΩ)

≤200

Rated Operating Frequency (times/h)

600

Latch Operating Frequency (times/h)

60

Mechanical Life (10,000 times)

100

Latch Life (10,000 times)

30

Contact Terminal Pressure (N)

>100

>150

Contact Gap (mm)

5/6±0.5

Overtravel (mm)

1.5±0.5

Weight (Kg)

26/30