渭南Outdoor high-voltage vacuum switch type prepaid metering device
Product Description
Product Overview
The JLSZK-10W prepaid combination current transformer is suitable for 50HZ rated, 10KV rated voltage three-phase power lines, realizing prepaid electricity metering, remote control, meter reading, and anti-theft functions. This product has a compact structure, powerful functions, small size and light weight, safety and reliability, and easy installation.
This product consists of a high-voltage main box and a control box. The high-voltage main box consists of a high-voltage current transformer chamber and a high-voltage vacuum contactor chamber. The high-voltage primary lead is led out through a high-voltage silicone rubber bushing. The secondary lines and control lines are led out from the box and connected to the control box through K-type cables or plastic-sealed metal flexible tubes. The control box consists of an electricity meter, a control terminal, and a control circuit. The high-voltage current transformer consists of two or three components (two voltage transformers connected in V/V, two current transformers). The current transformer can be made into a double current ratio (at the secondary winding tap) according to user needs.
The control box door panel is equipped with on/off indicator lights. It can display the high-voltage operating status and the remaining electricity fee.
Vacuum Switch Technical Characteristics
| Parameter Name |
JCZ8F-160/12 |
CZ8F-250/12 |
JCZ8F-400/12 |
JCZ8F-630/12 |
| Rated voltage of main circuit (KV) |
12 |
12 |
12 |
122 |
| Rated current of main circuit (A) |
160 |
250 |
400 |
630 |
| Main circuit closing capacity (A/100 times) |
1600 |
2500 |
4000 |
6300 |
| Main circuit breaking capacity (A/10 times) |
1280 |
2000 |
3200 |
5000 |
| Ultimate breaking capacity (A/3 times) |
3200 |
4000 |
4500 |
6000 |
| Mechanical life (10,000 times) |
100 |
100 |
100 |
100 |
| Mechanical latch life (10,000 times) |
10 |
10 |
10 |
10 |
| Main circuit power frequency withstand voltage (break) (KV) |
42 |
42 |
42 |
42 |
| Lightning impulse withstand voltage (KV) |
75 |
75 |
75 |
75 |
| Control circuit power frequency withstand voltage (KV) |
2 |
2 |
2 |
2 |
| Rated operating frequency (times/h) |
300 |
300 |
300 |
300 |
| Mechanical latch operating frequency (times/h) |
30 |
30 |
30 |
30 |
Main Technical Parameters
◇Reference standards for this type of combination current transformer
GB1206-2006 (Current Transformer)
GB1207-2006 (Voltage Transformer)
GB17201-2007 (Combination Current Transformer)
DL/7725-2000 Technical conditions for ordering power current transformers, etc.
◇This type of combination current transformer is composed of single-phase voltage transformers and single-phase current transformers to form a three-phase transformer. The voltage transformer uses V/V-12 wiring.
◇Rated voltage 10KV
◇Rated frequency 50HZ
◇Rated insulation level 12/42/75KV
◇The rated voltage ratio of the voltage transformer is 10/0.1KV, accuracy class/rated load 0.2/20VA, and limit output 500VA.
◇The rated current ratio of the current transformer is 5-600/5, accuracy class/rated load 0.2S/10VA.
◇Rated load power factor COSφ=0.8 (lagging), current transformer instrument security factor FS≤10.
◇Ambient temperature: between -25℃ and 40℃. The daily average temperature does not exceed 30℃.
◇Surface creepage distance meets Class II pollution level.
◇Altitude: not exceeding 1000m.
Appearance and Installation Dimensions