平顶山ZN63A-12(VS1) indoor high-voltage vacuum circuit breaker

The ZN63A-12(VS1) type indoor high-voltage vacuum circuit breaker is a three-phase AC 50Hz indoor device with a rated voltage of 12kV. It can be used for control and protection of electrical facilities in factories, mines, enterprises, power plants, and substations.

Product Description

Product Overview

The ZN63A-12(VS1) indoor high-voltage vacuum circuit breaker is a three-phase AC 50Hz indoor device with a rated voltage of 12kV. It can be used for control and protection of electrical facilities in factories, enterprises, power plants, and substations. The ZN63A-12 indoor high-voltage vacuum circuit breaker can be installed in both trolley-type switchgear and fixed switchgear. This circuit breaker has advantages such as long life, simple maintenance, no pollution, no explosion hazard, and low noise. The operating mechanism is spring-energy storage type, which can be operated by AC or manually; and it is suitable for harsh working conditions such as frequent operation.

 

Working Principle

The energy required for the circuit breaker to close is supplied by the spring energy storage mechanism. The energy storage mechanism can be driven by an external power supply motor or manually. After energy storage is complete, the energy storage indicator shows "Energy Stored". At the same time, the energy storage switching switch cuts off the power supply of the energy storage motor, and the circuit breaker is in the ready-to-close state. During the closing operation, whether the "Close" button is pressed manually or the closing electromagnet is activated by remote operation, the circuit breaker can be closed. After the closing operation is completed, the energy storage indicator and energy storage switching switch reset, the motor power is turned on, and the motor stores energy again. The closing indicator shows "Closed", and the auxiliary switch contacts are switched. During the tripping operation, whether the "Trip" button is pressed manually or the closing electromagnet is activated by remote operation, the circuit breaker can be tripped. After the tripping operation is completed, the tripping indicator shows "Tripped", and the auxiliary switch contacts are switched. At the same time, during the tripping operation, the counter automatically advances one position, and the corresponding number can be seen from the panel viewing window.

 

Serial Number

Name

Unit

Value

1

Rated Voltage

KV

12

2

Rated Insulation Level

1min Power Frequency Withstand Voltage

KV

42

Impulse Withstand Voltage

75

3

Rated Current

A

 

60

120

12501600

20002500

 

125016002000250031504000

 

4000

5000

4

Rated Short-Circuit Breaking Current

 

 

kA

20

25

31.5

40

50

5

Rated Short-Circuit Making Current (Peak)

50

63

80

100

130

6

Rated Dynamic Stability Current (Peak)

50

63

80

100

130

7

Rated Thermal Stability Current (RMS)

20

25

31.5

40

50

 

8

Rated Short-Circuit Breaking

Current Breaking Times

31.5kA

 

Times

50

40kA

30

50KA

20

9

Rated Thermal Stability Time

s

4

10

Rated Operating Sequence

 

Trip-0.3s-Close-Trip-180s-Close-Trip

Trip-180s-Close-Trip-180s-Close-Trip

 

11

 

Mechanical Life

31.5kA

 

Times

30000

40kA

20000

50KA

10000

12

Rated Single Capacitor Group Breaking Current

A

630

13

Rated Back-to-Back Capacitor Group Breaking Current

A

400

14

Operating Mechanism Rated Closing/Tripping Voltage (DC)

V

100/200

15

Three-Phase Trip/Close Asynchronism

ms

≤2

16

Contact Closing Bounce Time

ms

≤2

17

Average Tripping Speed

m/s

0.91.2

18

Average Closing Speed

m/s

0.40.8