马鞍山ZW20-12 series outdoor intelligent high-voltage vacuum circuit breaker

The ZW20-12 series outdoor pole-mounted intelligent high-voltage circuit breaker adopts a miniaturized spring operating mechanism design, making it more stable and reliable. The enclosure uses sealing, explosion-proof, and insulation technology, with good overall sealing performance. This product uses vacuum arc extinguishing and SF6 gas as the insulation medium, making it a maintenance-free, high-quality pole-mounted circuit breaker.

Product Description

Product Overview

The ZW20-12 series outdoor pole-mounted intelligent high-voltage circuit breaker adopts a miniaturized spring operating mechanism design, making it more stable and reliable. The enclosure uses sealing, explosion-proof, and insulation technology, with good overall sealing performance. This product uses vacuum arc extinguishing and SF6 gas as the insulating medium, and is a maintenance-free, high-quality pole-mounted circuit breaker product.

This product is mainly used for: switching on and off the load current and short-circuit current of the 10KV power system, suitable for substations and industrial and mining enterprises. It is equipped with an intelligent controller to protect and isolate faults in the power system; it is widely used in occasions with frequent grid operations. This circuit breaker can meet the various requirements of power automation control in conjunction with an intelligent controller and meets the corresponding technical standards required by the State Grid.

 

Operating Environment

◇ Ambient air temperature: -30℃~+40℃;

◇ Altitude: No more than 2000m;

◇ The surrounding air may be contaminated by dust, smoke, corrosive gases, steam, or salt spray;

◇ Wind speed does not exceed 34m/s without frequent violent vibrations;

◇ Pollution level: Level Ⅲ.

 

Technical Parameters

Serial Number

Item Name

Unit

Parameter

1

Rated Voltage

kV

12/24

2

Rated Frequency

Hz

50

3

Rated Current

A

630/1000

4

Rated Short-Circuit Breaking Current

kA

12.5/16/20/25

5

Rated Peak Withstand Current (Peak)

kA

31.5/40/50/63

6

Rated Short-Time Withstand Current (4S)

kA

12.5/16/20/25

7

Rated Short-Circuit Making Current (Peak)

kA

31.5/40/50/63

8

Mechanical Life

Times

10000

9

Rated Short-Circuit Breaking Current Breaking Times

Times

30

10

1min Power Frequency Withstand Voltage (Phase-to-Phase/Phase-to-Ground/Open Circuit)

kV

42/49/60

11

Lightning Impulse Withstand Voltage Peak (Phase-to-Phase/Phase-to-Ground/Open Circuit)

kV

75/85/125

12

Secondary Circuit 1min Power Frequency Withstand Voltage

kV

2

13

Net Weight

kg

140

14

SF6 Gas Rated Gauge Pressure

Mpa

0

 

Dimensional Drawing