都匀JCZ1-40.5KV

The vacuum tube's moving conductor is connected to the insulator, connecting rod, contact spring, and cantilever via a rotating shaft. When closing, the closing circuit energizes the closing coil via an auxiliary switch, driving the connecting rod to rotate the shaft upward, simultaneously moving the cantilever upward. This action closes the contacts within the vacuum tube via the contact spring, providing contact pressure to ensure reliable closure without bounce. During the holding state, the auxiliary switch is open, and the holding coil is energized, maintaining the contactor in the closed state. When the power supply circuit is de-energized, the contactor opens, driving the shaft downward. Simultaneously, the contact spring's and opening spring's restoring forces separate the vacuum tube contacts by a specified distance, ensuring reliable opening.

Product Description

Technical Parameters

Name

JCZ1-

160/40.5

JCZ1-

250/40.5

JCZ1-

400/40.5

JCZ1-

630/40.5

Main Circuit Rated Voltage (KV)

Main (KV)

40.5

40.5

40.5

40.5

Main Circuit Rated Current (A)

Main circuit rated current (A)

160

250

400

630

Rated Frequency (Hz)

Rated frequency (Hz)

50

50

50

50

Power Frequency Withstand Voltage (KV)

Power-frequency withstand voltage (KV)

95

95

95

95

Rated Closing Current (100 times)

Rated break current (100 Ops.)

3200

4000

4500

6000

Rated Breaking Current (50 times)

Rated break current (50 Ops.)

3000

3500

4000

5000

Maximum Breaking Current (3 times)

Maximum break current (3 Ops.)

3200

4000

4500

6000

Tripping Time (ms)

Opening time (ms)

≤50

≤50

≤50

≤50

Closing Time (ms)

Opening time (ms)

≤100

≤100

≤100

≤100

Contact Gap (mm)

Clearance between open contacts (mm)

15±1

15±1

15±1

15±1

Overtravel (mm)

Over travel (mm)

≥2

≥2

≥2

≥2

Mechanical Life (times)

Mechanical life (ops.)

100000

100000

100000

100000

Electrical Life AC3 (times)

Electrical life AC3 (ops.)

50000

50000

50000

50000

 

Figure 1 JCZ1 Series Single-Pole Outline Structure and Installation Dimensions

(Outline and installation size)

 

 

Figure 2 JCZ1 Series Three-Pole Outline Structure and Installation Dimensions

(Outline and installation size)

 

Figure 3 JCZ1-NSD Series External Wiring Diagram

Note: After the contactor terminals 1 and 2 are connected to the power supply, the contactor begins to store energy, and the energy storage indicator light starts to flash (the contactor cannot be switched on or off during the flashing period). When the energy storage is complete, the energy storage indicator light is always on. Press the closing button to close the contactor, and press the tripping button or disconnect the power supply at terminals 1 and 2 to trip the contactor. (The dashed box shows the internal wiring of the contactor.)