保定HX-800 series intelligent boundary switch controller
Category:
Product Description
Product Overview
This product uses a large 160*160 LCD screen with full Chinese display and 12 independent keys. It collects three-phase current, zero-sequence current, and PT voltage. By monitoring the values of these analog signals in real time and comparing them with set values, it can determine line faults and perform corresponding processing. This product has functions such as automatic single-phase grounding fault elimination, interphase short-circuit fault isolation, overload disconnection, undervoltage/overvoltage protection, ensuring the power safety of non-faulty users. It also has local and remote control on/off switch functions. The internal core uses a 32-bit ARM high-speed microcontroller as the main control chip, with advantages such as fast running speed, sensitive and accurate detection, and timely and rapid protection action. The product has local/remote control on/off switch functions, and communication methods such as local serial port parameter setting, GSM SMS control, and GPRS wireless communication are available.
Functions
◇Fast-break protection ◇Overcurrent acceleration ◇Overvoltage tripping ◇Status query
◇Time-limited fast-break protection ◇Three-time reclosing ◇Undervoltage tripping ◇Event recording
◇Overcurrent protection ◇Power-on closing ◇Real-time clock ◇GPRS communication
◇Three-stage protection ◇Loss-of-voltage tripping ◇Access control ◇UPS power supply
Main Technical Parameters
| Serial Number |
Item |
Specified Value |
Remarks |
| 1 |
Operating Voltage |
AC220V |
+150 |
| 2 |
Operating Voltage Frequency |
50Hz |
|
| 3 |
Overall Power Consumption |
<10W |
|
| 4 |
Output Control Method (Closing/Tripping Operation) |
Normally Open Contact |
Optional, load capacity 250V/5A |
| 5 |
6-way switch quantity input loop |
Optional |
AC/DC220V;AD/CD110V;DC24V |
| 6 |
Phase Current Sampling Input Value Range |
0~30A |
Secondary Value |
| 8 |
Zero-sequence Current Sampling Input Value Range |
0~10A |
Secondary Value |
| 9 |
Phase Current Sampling Error |
±0.5% |
|
| 10 |
Zero-sequence Current Sampling Error |
±0.2% |
|
| 11 |
Interphase Short-Circuit Overcurrent Protection Set Value |
0.5~30A |
Secondary Value (step 0.01A) |
| 12 |
Interphase Short-Circuit Overcurrent Protection Action Time |
0~3S |
Secondary Value (step 0.01S) |
| 13 |
Single-Phase Grounding Protection Current Set Value |
0.01~5A |
Secondary Value (step 0.005A) |
| 14 |
Single-Phase Grounding Protection Time Set Value |
0~30S |
Secondary Value (step 0.01S) |
| 15 |
Remote Control Distance |
Within 50 meters |