    High-voltage permanent magnet series vacuum switch technical parameters

    Parameter Name

    Unit

    250/12

    400/12

    630/12

    Main circuit rated voltage

    (KV)

    12

    12

    12

    Main circuit rated current

    (A)

    250

    400

    630

    Mechanical life

    (10,000 times)

    100

    100

    100

    Main circuit contact power frequency withstand voltage

    (KV)

    42

    42

    42

    Phase-to-phase; phase-to-ground power frequency withstand voltage

    (KV)

    Lightning impulse withstand voltage

    (KV)

    75

    75

    75

    Control circuit withstand voltage

    (KV)

    2

    2

    2

    Closing time

    (MS)

    30±5

    30±5

    30±5

    Opening time

    (MS)

    20±5

    20±5

    20±5

    Closing bounce time

    (MS)

    <3

    <3

    <3

    Opening bounce time

    (MS)

    <1

    <1

    <1

    Contact gap

    (MM)

    7±0.5

    7±0.5

    7±0.5

    Overtravel

    (MM)

    2±0.5

    2±0.5

    2±0.5

     

    Low-voltage permanent magnet series vacuum switch technical parameters

    Parameter Name

    Unit

    250/1.4

    400/1.4

    630/1.4

    Main circuit rated voltage

    (KV)

    1.4

    1.4

    1.4

    Main circuit rated current

    (A)

    250

    400

    630

    Main circuit making capacity

    (A/100 times)

    2500

    4000

    6300

    Main circuit breaking capacity

    (A/50 times)

    2000

    3200

    5000

    Ultimate breaking capacity

    (A/3 times)

    4500

    4500

    6300

    Electrical life (AC3)

    (10,000 times)

    60

    60

    60

    Electrical life (AC4)

    (10,000 times)

    6

    6

     

    Rated operating frequency

     

    0.1-0.15

    0.1-0.15

    0.1-0.15

    Mechanical life

    (10,000 times)

    300

    300

    300

    Rated operating frequency AC3

    (times/h)

    600

    600

    600

    Rated operating frequency AC4

    (times/h)

    120

    120

    120

    Contact gap

    (MM)

    2±0.2

    2±0.2

    2±0.2

    Overtravel

    (MM)

    1±0.2

    1±0.2

    1±0.2

     

     