KYN28A-12(Z) Metal-clad, center-mounted AC switchgear
KYN28A-12(Z)(GZS1) Metal-clad withdrawable AC switchgear (hereinafter referred to as "switchgear") is suitable for three-phase AC 50Hz power systems. It is used to receive and distribute electrical energy and to control, protect, and monitor circuits.
Keywords:
KYN28A-12(Z) Metal-clad, center-mounted AC switchgear
Category:
- Product details
-
- Commodity name: KYN28A-12(Z) Metal-clad, center-mounted AC switchgear
KYN28A-12(Z)(GZS1) Metal-clad withdrawable AC switchgear (hereinafter referred to as "switchgear") is suitable for three-phase AC 50Hz power systems. It is used to receive and distribute electrical energy and to control, protect, and monitor circuits.
Product Overview
KYN28A-12(Z)(GZS1) Metal-clad withdrawable AC switchgear (hereinafter referred to as "switchgear") is suitable for three-phase AC 50Hz power systems. It is used for receiving and distributing electrical energy and for controlling, protecting, and monitoring circuits.
This product conforms to the following standards: GB3906 "3.6-40.5KV AC metal-clad switchgear and control equipment", GB/T11022 "Common technical requirements for high-voltage switchgear and control equipment", IEC62271:200 "AC metal-enclosed switchgear and control equipment with rated voltage above 1KV and below 52KV", DL/T404 "Technical conditions for ordering indoor AC high-voltage switchgear".
Technical Parameters
Item
Unit
Data
Rated Voltage
KV
3.6、7.2、12
Rated Frequency
Hz
50
Circuit Breaker Rated Current
A
630、1250、1600、2000、2500、3150、4000
Switchgear Rated Current
A
630、1250、1600、2000、2500、3150、4000
Rated short-time withstand current (4s)
KA
16、20、25、31.5、40、50
Rated peak withstand current (peak)
KA
40、50、63、80、100、25
Rated short-circuit breaking current
KA
16、20、25、31.5、40、50
Rated short-circuit making current (peak)
KA
40、50、63、80、100、25
Rated insulation level
1min power frequency withstand voltage
Between poles, between poles and ground
KV
24.32、42
Between contacts
KV
24、32、48
Lightning impulse withstand voltage (peak)
Between poles, between poles and ground
KV
40、60、75
Between contacts
KV
46.70.85
Protection Grade
The enclosure is IP4X, and it is IP2X when the compartment doors and circuit breaker chamber doors are open.
Product Structural Features
1、 Switchgear structure (see Figure 1).
2、 Fully metal-clad, assembled structure, wide range of combination schemes.
3、 The cabinet uses imported aluminum-zinc coated thin steel plates, processed by MINGE machine tools, adopts advanced multiple crimping technology, and is connected by rivet nuts and high-strength bolts. It features high precision, light weight, high strength, and strong parts commonality.
4、 It can be equipped with VS1-24 series or imported VD4 series vacuum circuit breakers, which are widely applicable, highly reliable, and maintenance-free for many years.
5、 The truck has working and testing positions, and each position has a positioning and display device, which is safe and reliable.
6、 Various trucks are modular and interchangeable, ensuring that trucks of the same specification can be freely interchanged, while trucks of different specifications cannot be entered.
7、 Grounding switch installation methods: (1) Installed in the middle of the cabinet (front-mounted) for easy double-sided maintenance from the rear of the cabinet (Figure 1-a). (2) Installed at the rear of the cabinet (rear-mounted) to save space and area when installed against the wall (Figure 1-b).
8、 Current transformer installation methods: (1) Positive installation in the rear cable compartment; (2) Hanging installation at the bottom of the large bend plate.
9、 The cable compartment can accommodate up to 9 single-core cables.
10、 Each high-voltage compartment has a pressure relief channel to ensure personal safety.
11、 Highly reliable interlock device, fully meeting the "five-prevention" safety requirements.
12、 The truck is transported by a special carrier, making operation convenient and flexible.
13、 The front and rear doors are equipped with observation windows for convenient observation of the working status of the internal components.
Dimensions (see Figure 2, Table 2)
Height B
2300(2200)
Width A
Branch busbar rated current ≤1250A, thermal stability current 40KA
800(650)
Branch busbar rated current ≥1600A
1000
Depth C
Cable entry and exit
1500
Overhead entry and exit
1660
Dimensions (see Figure 3, Table 3)
Cabinet width A
Cabinet depth B
L1
L2
L3
L4
800
1500 cable
530
630
150
490
1660 overhead
530
630
310
650
1000
1500 cable
730
830
150
490
1660 overhead
730
830
310
650