KYN28A-12(Z) Metal-clad, center-mounted AC switchgear

KYN28A-12(Z)(GZS1) Metal-clad withdrawable AC switchgear (hereinafter referred to as "switchgear") is suitable for three-phase AC 50Hz power systems. It is used to receive and distribute electrical energy and to control, protect, and monitor circuits.

Keywords:

KYN28A-12(Z) Metal-clad, center-mounted AC switchgear

Telephone:

  • Product details
    • Commodity name: KYN28A-12(Z) Metal-clad, center-mounted AC switchgear

    KYN28A-12(Z)(GZS1) Metal-clad withdrawable AC switchgear (hereinafter referred to as "switchgear") is suitable for three-phase AC 50Hz power systems. It is used to receive and distribute electrical energy and to control, protect, and monitor circuits.

    Product Overview

    KYN28A-12(Z)(GZS1) Metal-clad withdrawable AC switchgear (hereinafter referred to as "switchgear") is suitable for three-phase AC 50Hz power systems. It is used for receiving and distributing electrical energy and for controlling, protecting, and monitoring circuits.

    This product conforms to the following standards: GB3906 "3.6-40.5KV AC metal-clad switchgear and control equipment", GB/T11022 "Common technical requirements for high-voltage switchgear and control equipment", IEC62271:200 "AC metal-enclosed switchgear and control equipment with rated voltage above 1KV and below 52KV", DL/T404 "Technical conditions for ordering indoor AC high-voltage switchgear".

     

    Technical Parameters

    Item

    Unit

    Data

    Rated Voltage

    KV

    3.6、7.2、12

    Rated Frequency

    Hz

    50

    Circuit Breaker Rated Current

    A

    630、1250、1600、2000、2500、3150、4000

    Switchgear Rated Current

    A

    630、1250、1600、2000、2500、3150、4000

    Rated short-time withstand current (4s)

    KA

    16、20、25、31.5、40、50

    Rated peak withstand current (peak)

    KA

    40、50、63、80、100、25

    Rated short-circuit breaking current

    KA

    16、20、25、31.5、40、50

    Rated short-circuit making current (peak)

    KA

    40、50、63、80、100、25

     

    Rated insulation level

    1min power frequency withstand voltage

    Between poles, between poles and ground

    KV

    24.32、42

    Between contacts

    KV

    24、32、48

    Lightning impulse withstand voltage (peak)

    Between poles, between poles and ground

    KV

    40、60、75

    Between contacts

    KV

    46.70.85

    Protection Grade

    The enclosure is IP4X, and it is IP2X when the compartment doors and circuit breaker chamber doors are open.

     

    Product Structural Features

    1、 Switchgear structure (see Figure 1).

    2、 Fully metal-clad, assembled structure, wide range of combination schemes.

    3、 The cabinet uses imported aluminum-zinc coated thin steel plates, processed by MINGE machine tools, adopts advanced multiple crimping technology, and is connected by rivet nuts and high-strength bolts. It features high precision, light weight, high strength, and strong parts commonality.

    4、 It can be equipped with VS1-24 series or imported VD4 series vacuum circuit breakers, which are widely applicable, highly reliable, and maintenance-free for many years.

    5、 The truck has working and testing positions, and each position has a positioning and display device, which is safe and reliable.

    6、 Various trucks are modular and interchangeable, ensuring that trucks of the same specification can be freely interchanged, while trucks of different specifications cannot be entered.

    7、 Grounding switch installation methods: (1) Installed in the middle of the cabinet (front-mounted) for easy double-sided maintenance from the rear of the cabinet (Figure 1-a). (2) Installed at the rear of the cabinet (rear-mounted) to save space and area when installed against the wall (Figure 1-b).

    8、 Current transformer installation methods: (1) Positive installation in the rear cable compartment; (2) Hanging installation at the bottom of the large bend plate.

    9、 The cable compartment can accommodate up to 9 single-core cables.

    10、 Each high-voltage compartment has a pressure relief channel to ensure personal safety.

    11、 Highly reliable interlock device, fully meeting the "five-prevention" safety requirements.

    12、 The truck is transported by a special carrier, making operation convenient and flexible.

    13、 The front and rear doors are equipped with observation windows for convenient observation of the working status of the internal components.
     

     

    Dimensions (see Figure 2, Table 2)

    Height B

     

    2300(2200)

    Width A

    Branch busbar rated current ≤1250A, thermal stability current 40KA

    800(650)

    Branch busbar rated current ≥1600A

    1000

    Depth C

    Cable entry and exit

    1500

    Overhead entry and exit

    1660

     

     

    Dimensions (see Figure 3, Table 3)

    Cabinet width A

    Cabinet depth B

    L1

    L2

    L3

    L4

    800

    1500 cable

    530

    630

    150

    490

    1660 overhead

    530

    630

    310

    650

    1000

    1500 cable

    730

    830

    150

    490

    1660 overhead

    730

    830

    310

    650

Related Products

Online Message

We will contact you within one working day. Please pay attention to your email.