Outdoor high-voltage split-type prepaid metering device

This product is a combination of a high-voltage metering device and a ZW43 intelligent sectionalizing switch, suitable for outdoor power systems with a rated frequency of 50HZ and a rated voltage of 10KV or less for electricity metering.

Keywords:

Outdoor high-voltage split-type prepaid metering device

Telephone:

  • Product details
    • Commodity name: Outdoor high-voltage split-type prepaid metering device

    This product is a combination of a high-voltage metering device and a ZW43 intelligent sectionalizing switch, suitable for outdoor power systems with a rated frequency of 50HZ and a rated voltage of 10KV or less for electricity metering.

    Product Overview

    This product is a combination of a high-voltage metering device and a ZW43 intelligent sectionalizing switch, suitable for outdoor power systems with a rated frequency of 50HZ and a rated voltage of 10KV or less for electricity metering. The current transformer uses fully enclosed epoxy resin vacuum casting, thus eliminating aging problems. The sectionalizing switch uses a vacuum switch and is equipped with zero-sequence and protective current transformers. It achieves zero-sequence, overcurrent, and fast-break protection with the intelligent controller, automatically cutting off single-phase ground faults and automatically isolating interphase short-circuit faults, ensuring the power safety of non-faulty users. This product has FTU function to realize remote control of switch on/off; it also has GPRS remote control function (see "Intelligent Controller Description" below for details). This prepaid combined current transformer realizes the basic functions of a prepaid high-voltage metering box through a prepaid control terminal, such as prepayment of electricity fees by users, reminders before arrears, tripping after arrears, and delayed alarm. This product is easy to install and has a beautiful appearance.

     

    The main technical parameters of the circuit breaker are shown in the table

    Serial Number

    Name

    Unit

    Data

    1

    Rated Voltage

    KV

    12

    2

    1min Power Frequency Withstand Voltage (Dry) Phase-to-Phase/Phase-to-Ground/Open Circuit

    42/48

    Lightning Impulse Withstand Voltage (Peak) Phase-to-Phase/Phase-to-Ground/Open Circuit

    75/85

    3

    Rated Current

    A

    630/1250

    4

    Rated Short-Circuit Breaking Current

    KA

    12.5/20.5/25

    5

    Rated Capacitor Bank Breaking Current

    A

    400/630

    6

    Rated Short-Circuit Closing Current (Peak)

    KA

     

    31.5/50/63

    7

    Rated Peak Withstand Current

    8

    Rated Short-Time Withstand Current

    2.5/20.5/25

    9

    Mechanical Life

    Times

    10000

    10

    Contact Gap

    mm

    9±1

    11

    Contact Overtravel

    2.5±0.5

    12

    Allowable Wear Thickness of Moving Contact

    <3

    13

    Three-Phase Switching Time Difference

    ms

    ≤2

     

    Current Transformer Parameter Table

    Product Model

    Rated Voltage Ratio (V)

    Rated Current Ratio (A)

    Voltage Transformer Accuracy Class and Secondary Load (VA)

    Current Transformer Accuracy Class and Secondary Load (VA)

    Rated Short-Time Thermal Current (KA)

    Rated Insulation Level (KV)

    0.2

    0.5

    0.2S

    0.5S

    JLSZ-6

    6000/100

    5-300/5

    20

    20

    10

    10

    (80-100)*lin

    7.2/32/60

    JLSZ-10

    10000/100

    5-500/5

    20

    20

    10

    10

    12/42/75

     

    External Dimensions and Installation Diagram

     

Related Products

Online Message

We will contact you within one working day. Please pay attention to your email.